Cold air containment.
| Content Provider | CiteSeerX |
|---|---|
| Author | Pervilä, Mikko Kangasharju, Jussi |
| Abstract | This article describes two benchmark studies involving the cooling technique known as cold aisle containment (CAC). One test case studies a 26U server rack operating on unconditioned outside air only in a carefully controlled setup. The other examines a server room with a power draw of over 80 kW during normal operation. In both cases we measure how incorporating CAC changes the air flow, electricity consumption, operating temperatures, and cooling requirements. Our results show how the air flow separation affects the temperatures in the server room and verify that using CAC can reduce CRAC power by roughly a fifth. |
| File Format | |
| Access Restriction | Open |
| Subject Keyword | Cold Air Containment Server Room Cold Aisle Containment Air Flow Separation Cooling Technique Test Case Study Server Rack Cooling Requirement Air Flow Electricity Consumption Power Draw Incorporating Cac Benchmark Study Crac Power Normal Operation |
| Content Type | Text |
| Resource Type | Article |